Dry-type transformer manufacturers believe that debugging before operation of the transformer:
(1) Check the transformer ratio and wiring group, measure the DC resistance of the high and low voltage windings, and compare the results with the factory test data provided by the manufacturer.
(2) Check the insulation resistance between coils and between coils and ground. If the insulation resistance is significantly lower than the factory measurement data, it indicates that the transformer is damp. When the insulation resistance is lower than 1000/V (working voltage), the transformer must be dry.
(3) Dry-type transformer manufacturers believe that the test voltage of the withstand voltage test should comply with regulations. When doing the low-voltage withstand test, the temperature sensor TP100 must be taken out. After the test is completed, put the sensor back in place promptly.
(4) When the transformer is equipped with a fan, the fan should be powered on and ensure its normal operation.
Dry-type transformer manufacturers believe that there are three reasons for the lack of phase in the transformer:
1. The power supply is missing one phase;
2. One phase of the transformer high-voltage fuse is blown;
3. Due to careless transportation, the high-voltage lead is thin, causing the transformer to break due to vibration (but it is not grounded)

Dry-type transformer manufacturers believe that when the transformer is put into operation, if the tap changer is not in place, it will make a loud "chirp" sound, which may cause the high-voltage fuse to blow in severe cases; if the tap changer has poor contact, it will produce a slight "chirp" sound. "The sound of sparks and electricity. Once the load increases, the tap changer contacts may burn out. In this case, it is necessary to cut off the power supply and repair it in time.
Dry-type transformer manufacturers believe that when the through-hole screws clamping the iron core of the transformer are loose and nut parts or small metal objects are left on the iron core and fall into the transformer, the transformer will make a "dinging" knocking sound or blowing sound and similar sounds. There is a "squeaking" sound from the magnet holding the small shim, but the voltage, current and temperature of the transformer are normal. This situation generally does not affect the normal operation of the transformer and can be handled by a power outage.