Home-Knowledge-

Content

Grounding Transformer: Structure and Core Steel Selection

Jan 29, 2024

What a Grounding Transformer Does

A grounding transformer provides a neutral point on a system that has none, most commonly an unearthed or delta connected network. Once the neutral exists, a resistor or reactor can be connected to it, earth fault current is limited to a chosen value, and protective relays have a measurable quantity to work with. It also provides a return path for zero-sequence current and controls the transient overvoltages that appear during arcing earth faults.

The duty is fundamentally different from that of a power transformer. A grounding transformer carries current only during an earth fault, so it is rated for a short-time current rather than a continuous power rating. IEEE Std C57.32 covers neutral grounding devices including grounding transformers and reactors, and defines the terminology, ratings and test requirements for that duty.

Winding Arrangements and Their Behaviour

Arrangement How it works Typical use
Zig-zag, also called interconnected star Phase windings on each limb are wound in opposite directions so that positive and negative sequence currents cancel while zero-sequence current finds a low impedance path The standard arrangement where a neutral is needed with low zero-sequence impedance
Wye-delta, with the delta closed The delta provides a circulating path for zero-sequence current while the wye gives the neutral point Used where a delta secondary is already required for other duties
Three single-phase units connected in zig-zag Same electrical behaviour, built from three cores Large ratings and sites where single-phase transport is easier

The zig-zag arrangement is the commoner choice because it presents a low zero-sequence impedance without needing a delta winding, which keeps the unit compact. Its short-time rating and duration, commonly expressed as a current for a period such as ten seconds, are set by the protection clearing time and the thermal capacity of the winding.

Core Steel and Winding Materials

The core is laminated from grain-oriented electrical steel, because the flux path in the limbs is fixed and unidirectional during the earth fault, which is precisely the condition where oriented material gives the lowest core loss and the highest magnetic induction. Grades such as 30Q120 under GB/T 2521.1, meaning 0.30 mm thickness with a maximum specific loss of 1.20 W/kg, are typical. The core is built with the rolling direction aligned along the limb and is clamped so that pressure is controlled, since over-compression degrades magnetic properties and under-clamping causes core noise and movement.

Windings are copper, chosen for conductivity and for thermal capacity during the short-time duty. Insulation systems follow the temperature class of the design, and the dielectric clearances satisfy the impulse and power frequency tests required by IEC 60076-3 for the transformer itself. For dry-type units the relevant standard is GB/T 1094.11 for dry-type power transformers, and IEEE Std C57.12.01 applies to dry-type transformers in the North American market.

Tank, Enclosure and Corrosion Protection

Oil-immersed grounding transformers use a steel tank with a sealed cover, while dry-type and pad-mounted units use a sheet steel enclosure. Both are corrosion protected, and the material choice is the same family used for transformers and switchgear generally.

Tanks and enclosures are formed from galvanized or zinc-aluminum-magnesium coated steel sheet, typically 2 to 3 mm thick, with ZM or Z275 designations where continuously coated material is used.

Fabricated frames, brackets and welded assemblies are hot-dip galvanized after fabrication to ISO 1461 or GB/T 13912, so that the coating covers inside corners and the insides of hollow members that painting cannot reach.

Degree of protection for the enclosure follows IEC 60529, with outdoor units commonly specified as IP23 for ventilated designs with a weatherproof canopy, or IP54 where total dust and splash protection is required.

Coating mass is verified per lot, and cut edges of coated sheet are treated with a zinc-rich repair compound applied to the practice in ASTM A780.

Selection, Testing and Quality Control

State the system voltage, the required earth fault current, the duration of the fault for which the unit must carry that current, and the zero-sequence impedance the protection scheme assumes.

Core magnetic properties are verified from production lot data, with specific loss and magnetic polarisation tested on an Epstein frame to IEC 60404-2 or by single sheet test to IEC 60404-3.

Routine electrical tests cover winding resistance, ratio, insulation resistance, applied voltage and induced voltage tests, with temperature rise verified against the design class.

Materials are certified separately, with EN 10204 3.1 certificates for the core steel, the winding conductor and the coated steel used for the tank or enclosure.

Dimensional and coating checks are performed on the finished enclosure before dispatch, including coating thickness measured by the magnetic method of ISO 2178.

Frequently Asked Questions

Q: Why is a grounding transformer rated in seconds rather than in kilovolt-amperes?

A: Because it only carries current during an earth fault. The rating that matters is the current it can carry for the time the protection takes to clear the fault, so the unit is specified by short-time current and duration.

Q: What is the advantage of a zig-zag winding?

A: It provides a low impedance path for zero-sequence current without a delta winding, so the neutral can be established with a more compact and economical core and winding arrangement.

Q: Which core steel is used?

A: Grain-oriented electrical steel, since the flux path in the limbs is unidirectional during the fault. Grades with about 3% silicon and a specific loss in the region of 1.20 W/kg at 0.30 mm thickness are typical.

Q: Why is the enclosure hot-dip galvanized rather than painted?

A: Hot-dip galvanizing coats the inside of hollow members, internal corners and weld areas that paint cannot reliably reach, which is where corrosion starts in outdoor transformer enclosures.

Q: Can a grounding transformer be used continuously?

A: Standard units are built for short-time duty. If continuous zero-sequence current is expected, the design must be rated for it explicitly, because the thermal limit of the winding is set by the rated duration.

SEND INQUIRY

SEND INQUIRY