Home-Knowledge-

Content

Adjustment method of power transformer output voltage

Jan 23, 2024

A general three-phase transformer has a three-speed or five-speed voltage regulating switch, which can be used to adjust the primary voltage of the transformer.

20240123163504

Transformer voltage regulation steps:

(1) Power failure. Disconnect the load on the low-voltage side of the transformer, use an insulating rod to open the drop fuse on the high-voltage side, take necessary safety measures, unscrew the protective cover of the transformer tap-changer, and place the positioning pin in the zero position. (2) When adjusting the gear position, adjust the tap changer to the corresponding position according to the output voltage: when the transformer output value is lower than the allowed value, adjust the tap changer from first gear to second gear, or from second gear to third gear. . When the transformer output value is higher than the allowed value, adjust the tap changer from the third gear to the second gear, or from the second gear to the first gear. (3) After adjusting the gear, use a DC bridge to measure the DC resistance of each phase winding to check whether the current between each winding is balanced. If the difference in resistance value of each phase is greater than 2%, it must be readjusted. Otherwise, poor contact between the dynamic and static contacts after operation will generate heat and damage the transformer.