Let's introduce the backup protection of transformer. There are many types of backup protection configurations for transformers. Here we briefly introduce the two types of backup protection: complex voltage blocking overcurrent protection and grounding protection of transformers.

 

1. Re-voltage blocking over-current protection
The complex voltage blocking overcurrent protection is the backup protection for phase-to-phase short circuit faults of large and medium-sized transformers. It is suitable for step-up transformers, system contact transformers and step-down transformers whose overcurrent protection cannot meet the sensitivity requirements. The composite voltage composed of negative sequence voltage and low voltage can reflect various faults within the protection range, reduce the setting value of over-current protection, and improve the sensitivity.

step down transformer 220v to 110v

Composite voltage overcurrent protection consists of composite voltage components, overcurrent components, and time components. The access current of the protection is the secondary three-phase current of CT on the local side of the transformer, and the access voltage is the secondary three-phase voltage of PT on this side of the transformer or other sides. For microcomputer protection, the voltage on one side can be provided to other sides through software, thus ensuring that the re-voltage overcurrent protection can still be used during PT maintenance on any side.

3 phase transformer

2. Ground protection of transformer
The backup protection for ground short-circuit faults of large and medium-sized transformers usually includes: zero sequence overcurrent protection, zero sequence overvoltage protection, gap protection, etc. The following is a brief introduction based on the three different grounding methods of the neutral point.


(1) The neutral point is directly grounded
For transformers with a voltage of 110kV and above and a neutral point directly grounded, a zero-sequence current protection that responds to ground faults should be installed on the high-current grounding system side. For transformers with both high and middle sides directly grounded, the zero-sequence current protection should be oriented, and the direction should be directed towards the busbars on each side.

 

The principle of zero sequence current protection is similar to the zero sequence protection of lines. The zero sequence current can be taken from the neutral point CT secondary current, or it can be self-produced by the local CT secondary three-phase current. The zero-sequence voltage connected to the directional element can be taken from the PT open delta voltage on this side, or it can be self-produced by the secondary three-phase voltage on this side. Among microcomputer protection devices, self-produced methods are mainly adopted.

 

For large three-winding transformers, the zero-sequence current protection can be three-stage. Among them, segment I and segment II have direction, and segment III does not have direction. Each section generally has two levels of delay. A shorter delay is used to reduce the fault scope (tripping the bus coupler or strip-side switch), and a longer delay is used to cut off the transformer (tripping the three-side switch). The specific protection configuration is determined based on the actual situation.

 

(2) The neutral point is not grounded
The zero-sequence current passes through the neutral point of the transformer to form a zero-sequence loop. However, if the neutral points of all transformers are grounded, the short-circuit current at the ground point will be shunted to each transformer, which will cause the zero-sequence overcurrent protection sensitivity to decrease. Therefore, in order to limit the zero-sequence current within a certain range, there are regulations on the number of transformers operating with neutral points grounded.

 

For transformers operating without grounding, in order to prevent overvoltage damage to the transformer caused by gap arcing at the fault point during a ground fault, zero sequence voltage protection should be configured.

 

Due to the high insulation level of the neutral point of a fully insulated transformer, when a ground fault occurs in the system, zero-sequence current protection is first used to remove the neutral point from being grounded. If the fault still exists, zero-sequence voltage protection is used to remove the neutral point from being grounded. of transformers.

 

(3) The neutral point is grounded through the discharge gap
Ultra-high voltage transformers are all semi-insulated transformers, and the insulation of the neutral point coil to ground is weaker than that of other parts. Neutral point insulation is prone to breakdown. Therefore, gap protection needs to be configured.

 

The function of gap protection is to protect the insulation safety of the neutral point of an ungrounded transformer.

 

Install a breakdown gap between the transformer neutral point and ground. When the ground isolation switch is closed, the transformer is directly grounded and zero sequence overcurrent protection is enabled. When the grounding isolating switch is disconnected, the transformer is grounded through the gap and put into gap protection.

 

Gap protection is implemented using the gap current 3I0 flowing through the neutral point of the transformer and the busbar PT opening triangle voltage 3U0 as criteria.

 

If the fault neutral point rises relative to the ground point, the gap breaks down and a large gap current 3I0 is generated. At this time, the gap protection operates and the transformer is cut off after a delay. In addition, when a ground fault occurs in the system, the neutral point is grounded to run the transformer zero sequence protection action, and the transformer with the neutral point grounded is first removed. After the system loses the grounding point, if the fault still exists, the open delta voltage 3U0 of the busbar PT will be very large, and the gap protection will also act at this time.